Injection nozzles
The injection nozzles for chlorine are appropriately
combined fittings via which the chlorine solution (hypochloric
acid) supplied by the full-vacuum chlorinators is introduced
into the water to be treated.
The injection nozzle assembly comprises an injection
pipe which is screwed into the water pipe, a shutoff
valve and a non-return valve.
The shutoff valve allows to separate the metering system
completely from the water supply, while the non-return
valve automatically prevents water flowing back to the
metering unit.
Selection criteria
The injection nozzle must be selected on the basis of
the water volume determined when dimensioning the ejector.
The throughput stated for the injection nozzle should
be equal to or higher than that for the ejector.
|